Why would I still need an overcurrent protector for my equipment that I am sending to the United Kingdom, since that plug already has a fuse in it?
Original equipment manufacturers routinely ask why their equipment would still need a circuit breaker or fuse given that the United Kingdom plug has a fuse. Ron Barnett, Product Development Manager, explains why an overcurrent protector for equipment when using the UK plug is still needed.
“Technically, the fuse in the plug is designed to protect the cable between the plug and the equipment in the case of a sudden short circuit. The key objective is to prevent the cable from overheating and causing a fire. If the equipment is connected to a UK Ring Main system, that sudden short circuit is sourced from two directions which can delay how soon the building’s miniature circuit breaker or fuse can clear the fault,” Barnett said.
The United Kingdom is the only country that requires a fused power plug. In addition to a traditional radial circuit (where cable terminates at the last outlet), a ring mains system is commonly used in homes and buildings in the UK. Circuits leave the local branch protection device, travel out to the loads (such as outlets or lamps), and then return to the circuit protection device. The fuse in the UK plug helps to minimize safety hazards associated with the ring mains system.
A fault condition at an outlet, for example, will be sourced with current from both directions. This minimizes the amount of heat generated in the conductor, as the fault condition occurs, but before the circuit protection device can clear the fault. By minimizing the heat generated, the degradation of insulation (which accompanies overheating due to repeated fault conditions) is also diminished, improving the long-term safety of the insulation system.
Until the circuit protection device clears the fault, however, the fault condition is sourced from two different directions in the supply system. There is, therefore, a much greater potential fault current condition. The secondary protection device at the plug minimizes the safety hazard this condition creates; hence the power plug fuse.
If you have other questions, Interpower offers free technical support. You can check the website at www.interpower.com, e-mail sales@interpower.com (United States) or uk@interpower.com (United Kingdom) or contact Customer Service in the United States at (800) 662-2290 or in the United Kingdom at +44 (0)1908 295300.